  1.     SECTION 13980
  2.  
  3.     RETROFIT-SPRINKLER PIPING COVER SYSTEM
  4.  
  5. NOTE ** This section is based on DecoShield piping cover systems manufactured by Creative Systems, Inc., headquartered at the following address:
  6. NOTE **      One Parker Place
  7. NOTE **      P.O. Box 957
  8. NOTE **      Janesville, WI  53547
  9. NOTE **      Telephone:  (608) 757-0717
  10. NOTE **      Fax:  (608) 757-0721
  11. NOTE ** 
  12. NOTE ** This section includes piping anchors and covers for retrofitted sprinkler systems installed in existing construction.  The covers and anchors are designed to be mounted against walls and ceilings; the covers are of L-shaped and U-shaped cross-section.  The entire system is UL listed and can be painted.
  13. NOTE ** 
  14. NOTE ** SECTION 13980 - RETROFIT-SPRINKLER PIPING COVER SYSTEM, Copyright 1996, The Architect's Catalog, Inc.
  15.  
  16. PART 1    GENERAL
  17.  
  18. 1.1    SECTION INCLUDES
  19. NOTE ** Delete items below not required for project.
  20.  
  21.     A.    Modular piping cover system for installation of metal piping system in existing construction.
  22.  
  23.     B.    Modular combination pipe hanger and cover system for installation of CPVC piping system in existing construction.
  24.  
  25. 1.2    RELATED SECTIONS
  26. NOTE ** Delete any sections below not relevant to this project; add others as required.  If piping is to be installed in this project, this section MUST be accompanied by a section that specifies the piping installation.  The only part of the piping installation that is included in this section is the actual hanger fitting that encircles the pipe and is attached to the wall or ceiling -- coordinate the piping specification.
  27.  
  28.     A.    Section 13915 - Fire Protection Piping.
  29.  
  30. 1.3    REFERENCES
  31. NOTE ** Delete references from the list below that are not actually required by the text of the edited section.
  32.  
  33.     A.    ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
  34.  
  35.     B.    NFPA 13 - Installation of Sprinkler Systems.
  36.  
  37.     C.    "Building Materials Directory"; Underwriters Laboratories Inc.
  38.  
  39.     D.    "Fire Protection Equipment Directory"; Underwriters Laboratories Inc.
  40.  
  41. 1.4    SUBMITTALS
  42.  
  43.     A.    Submit under provisions of Section 01300.
  44.  
  45.     B.    Product Data:  Include manufacturer's installation instructions.
  46.  
  47.     C.    Certification of UL listings.
  48.  
  49. 1.5    DELIVERY, STORAGE, AND HANDLING
  50.  
  51.     A.    Store materials in areas where temperature will be maintained above 35 degrees F.
  52.  
  53.     B.    Protect from exposure to direct sunlight.
  54.  
  55.     C.    Stack or store in such a manner to prevent distortion of shape.
  56.  
  57. 1.6    WARRANTY
  58.  
  59.     A.    Provide manufacturer's 10 year material warranty.
  60.  
  61.  
  62. PART 2    PRODUCTS
  63.  
  64. 2.1    MANUFACTURERS
  65.  
  66.     A.    Provide "DecoShield" piping cover system manufactured by Creative Systems, Inc., One Parker Place, P.O. Box 957, Janesville, WI 53547.  Telephone: (608) 757-0717.  Fax: (608) 757-0721.
  67.  
  68. 2.2    MATERIALS
  69.  
  70.     A.    Piping Cover System:  Modular, snap-fit cover units, clips, and anchors, which once assembled, render the cover essentially irremovable with the use of ordinary tools; UL listed for use with CPVC piping systems.
  71.  
  72.     B.    Cover Units:  L-shaped and U-shaped cross-section units of flame retardant resin material, paintable finish.
  73.         1.    Resin:  B.F. Goodrich Co. "TempRite."
  74.         2.    Surface burning characteristics when tested in accordance with ASTM E 84:
  75.             a.    Flame spread:  20.
  76.             b.    Smoke developed:  250.
  77.         3.    Unit length:  7.5 feet.
  78.         4.    Provide coupling fittings for joining units end to end and prefabricated inside and outside corner fittings and end caps.
  79. NOTE ** Delete the following paragraph if no sidewall sprinkler installations are included.
  80.         5.    Provide sidewall sprinkler head housing accommodating NFPA 13 4-inch drop assembly requirements.
  81.         6.    Provide mounting clips to secure covers to wall/ceiling.
  82.  
  83.     C.    Pipe Hangers for CPVC Piping:  Manufactured by cover system manufacturer; UL listed; requiring no special tools for installation.
  84.         1.    For supporting piping only:  "Snap-2" hangers.
  85.         2.    For supporting both piping and covers:  "Combo" hangers that automatically position pipe in cover.
  86.  
  87.     D.    Pipe Hangers for Copper and Steel Piping:  Design and dimensions compatible with cover system; UL listed.
  88. NOTE ** Delete the following paragraph if the covers are to be left unpainted or if painting is to be done by some entity other than the installer of the covers.  In the latter case, specify painting in Division 9.
  89.  
  90.     E.    Paint:  Acrylic latex; color to match adjoining surfaces.
  91.  
  92.  
  93. PART 3    EXECUTION
  94.  
  95. 3.1    INSTALLATION
  96.  
  97.     A.    Install in accordance with the manufacturer's instructions and recommendations.
  98. NOTE ** Delete the following paragraph if the covers are being installed on existing piping.  Otherwise, coordinate the section number and title with the actual section where the piping installation is specified.
  99.  
  100.     B.    See Section 13980 - Fire Protection Piping for requirements for installation of piping.  Space hangers supporting piping in accordance with applicable requirements.
  101.  
  102.     C.    Space hangers and mounting clips supporting covers to hold the covers and fittings firmly against the mounting surface without gaps or unpleasant appearance.
  103.  
  104.     D.    Install cover units using coupling fittings and corner units as required.
  105. NOTE ** Delete the following paragraph if the covers are to be left unpainted or if painting is to be done by some entity other than the installer of the covers.  In the latter case, specify painting in Division 9.
  106.  
  107.     E.    Paint entire cover assembly.  Cover sprinkler heads carefully during painting and remove covering completely immediately after painting.